SSD 605C Product Manual - page 228
Application Macros
15-1
4
605C Frequency Inverter
Macro 6: Closed-Loop Speed Feedback
Encoder speed feedback.
PID speed regulation loop.
Additional Operator Menu display parameters.
Terminal
Name
Purpose
Comment
1
ANALOG INPUT 1
Setpoint
0V = 0%, 10V = 100%
2
ANALOG INPUT 2
Setpoint Trim
0V = 0%, 10V = 100%
6
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand, 0V =
0%, 10V = 100%
13
DIGITAL INPUT 1
Run
24V = Run
14
DIGITAL INPUT 2
Trip Reset
0V to 24V transition to reset trips.
15
DIGITAL INPUT 3
Direction
0V = Forward, 24V = Reverse
16
DIGITAL INPUT 4
External Trip
0V = Trip (connect to terminal
18)
17
DIGITAL INPUT 5
PID Enable
0V = PID Disabled, 24V = PID
Enabled
21, 22
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
23, 24
DIGITAL OUTPUT 2
Running
0V = Stopped, 24V = Running
The Operator Menu System for Macro 6
The default Operator menu system is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
DC LINK VOLTS
CURRENT LIMITING
PID OUT SCALING
STARTUP SCREEN
PID P GAIN
PID I TIME CONST
PID D TIME CONST
PID FILTER TC
PID SETPOINT
PID FEEDBACK
PID ERROR
ENTER PASSWORD