Riverbed Steelhead CX Series Installation Manual - page 7
Rack Installation Guide
3
Required Tools and Equipment
Preface
The rack cannot have solid or restricted airflow doors. You must use a mesh door on the front and back
of the rack or remove the doors to ensure adequate airflow to the system.
The rack width and depth must allow for proper serviceability and cable management.
Ensure that there is adequate airflow in the rack. Improper installation or restricted airflow can
damage the equipment.
Models 150/250/550/CX255/CX555/CX755 are designed for the desktop. If you install them in a rack,
do not place equipment on top of the unit as it restricts airflow and might cause damage to the
equipment.
Make sure the product is properly mated with the rails. Products that are improperly mated with the
rails might be unstable.
Verify that the AC power supply branch circuit that provides power to the rack is not overloaded. This
will reduce the risk of personal injury, fire, or damage to the equipment. The total rack load should not
exceed 80 percent of the branch circuit rating. Consult the electrical authority having jurisdiction over
your facility wiring and installation requirements.
The 1U, 2U, and 3U systems produce front-to-back cooling airflow that requires an unobstructed
airflow to the fan housing. Do not mount the system near other electronic devices that produce back-
to-front airflow.
The Series x50 require sideways airflow. Do not block the sides.
The Series x50 require air-convection cooling. If these models are installed in a rack, use the Riverbed
provided rack-mount.
This device for use only in a machine room or IT room.
Make sure that the area in which you install the system is properly ventilated and climate-controlled.
Ensure that the voltage and frequency of your power source match the voltage and frequency inscribed
on the electrical rating label of the equipment.
Do not install the system in or near a plenum, air duct, radiator, or heat register.
Never use the product in a wet location.
For detailed safety information, see the Safety and Compliance Guide.
Required Tools and Equipment
You need the following tools and equipment to mount the system to a rack:
A standard Telco-type rack
A standard Phillips-head screwdriver
The enclosed screw kit
The enclosed short rack adaptors (if needed)
The enclosed square post-hole converters (if needed)
The enclosed brackets for mounting the Series x50 (if needed)
If your system is missing any components, please contact Riverbed Support for replacement parts at
https://support.riverbed.com.