106 Advanced Operations
Switched PDU
Installation and Operations Manual
Setting the SNMP v3 trap username:
The Set SNMP Trap Username command sets an optional username for display on SNMP activity logs to identify
user actions.
At the Switched CDU: prompt, type set snmp v3 trapusername, and press Enter. The trap username can be 1-31
alphanumeric characters; spaces are allowed; and the name is case sensitive.
Setting the error trap repeat timer:
The Set SNMP Traptime command sets the timer period between repeated error condition traps.
The valid range is 1 to 65535 (in seconds). The default is 60 seconds.
To set the error trap repeat timer:
At the Switched CDU: prompt, type set snmp traptime, followed by the timer period, and press Enter.
Example
The following sets the timer period to 180 seconds:
Switched PDU: set snmp traptime 180
Setting the SNMP trap format version:
The SNMP Trap Format configures the SNMP trap format version. The trap format can be SNMP v1, v2, or v3.
To set the trap format version:
At the Switched CDU: prompt, type set snmp trapformat, followed by 1, 2, or 3, and press Enter. The default is v1,
regardless of the versions that are enabled for the agent.
Example
The following sets the trap format version to SNMP v3:
Switched CDU: : set snmp trapformat 3
Setting IP Restrictions:
The Set SNMP IP Restrictions command supports SNMP Manager Get and Set requests to only be allowed from the
IP address of the defined trap destinations.
To set SNMP IP restrictions:
At the Switched CDU: prompt, type set snmp iprestrict trapdests and press Enter.
To remove SNMP IP restrictions:
At the Switched CDU: prompt, type set snmp iprestrict none and press Enter.
Setting trap destinations:
The Set SNMP Trapdest1 and Trapdest2 commands are used to set the IP addresses or hostname of SNMP
management stations receiving all traps. The Switched PDU supports a maximum of two trap destinations; one must
be defined to enable trap generation.
To set the trap destination:
At the Switched CDU: prompt, type set snmp, trapdest1 or trapdest2, the Ipaddress or hostname and press Enter.
Examples
The following sets the trap destination 1 to 64.42.31.208:
Switched CDU: set snmp trapdest1 64.42.31.208
The following sets the trap destination 2 to snmp.servertech.com:
Switched CDU: set snmp trapdest2 snmp.servertech.com
To reset the trap destination:
At the Switched CDU: prompt, type set snmp, trapdest1 or trapdest2, 0.0.0.0 and press Enter.