Switched PDU
Installation and Operations Manual
Operations 95
Displaying UPS configuration:
The Show UPS command displays information about all UPS devices.
UPS Type and Host/IP address
UPS SNMP port and community string
SNMP Objects OID values and expected return values
To display UPS configuration information:
At the Switched CDU: prompt, type show ups and press Enter.
Example
The following command displays UPS configuration information:
Switched CDU: show ups
1 Type: Liebert
Host/IP: DC1Liebert1
Voltage Polling: ON
SNMP Configuration
Community String: public
SNMP Port: 162
SNMP Objects/Expected Values
Voltage: .1.3.6.1.2.1.33.1.4.4.1.2.1
Utility Status: .1.3.6.1.2.1.33.1.4.1.0
On Battery: 0x5
On Utility: 0x3
More (Y/es N/o):
Feature Administration
Displaying activated special features:
The Show Features command displays all activated special features for the device.
To display activated special features:
At the Switched CDU: prompt, type show features and press Enter.
Example
The following command displays all activated special features:
Switched CDU: show features
Activated Features:
Smart Load Shedding
NOTE: A restart of the PDU is required after activating new special features.