Server Technology Switched Rack PDU Installation And Operation Manual - page 67
Switched PDU
Installation and Operations Manual
Operations 67
Displaying outlet information:
The Show Outlets command displays information about all outlets. This information includes:
Sequencing and reboot timer values
Descriptive outlet name, if applicable
Outlet wakeup state and post-on settings
Current outlet locked status
To display outlet information:
At the Switched CDU: prompt, type show outlets and press Enter.
Example
The following command displays all outlet information:
Switched CDU: show outlets
Outlet Outlet Wakeup Post-On
Locked
ID Name State Delay (seconds)
.A1 DataServer_1 On 0 Yes
.A2 WebServer_1 On 0 Yes
.A3 FileServer_1 On 0 No
.A4 TowerA_Outlet4 On 0 No
.A5 TowerA_Outlet5 On 90 No
.A6 TowerA_Outlet6 On 0 Yes
.A7 TowerA_Outlet7 On 0 No
.A8 TowerA_Outlet8 On 0 No
.A9 TowerA_Outlet9 On 0 No
.A10 TowerA_Outlet10 On 0 No
.A11 TowerA_Outlet11 On 0 No
.A12 TowerA_Outlet12 On 0 No
.A13 TowerA_Outlet13 On 0 No
.A14 TowerA_Outlet14 On 0 No
.A15 TowerA_Outlet15 On 0 No
.A16 TowerA_Outlet16 On 0 No
More (Y/es N/o):
Outlet Options:
Sequence Interval: 2 seconds
Reboot Delay: 15 seconds
Input Feed Administration
Creating a descriptive infeed name:
The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is displayed when the
Show Traps command is issued. For more information about the Show Traps command, see the “Displaying trap
configuration information” section.
To create a infeed name:
At the Switched CDU: prompt, type set infeed name followed by the absolute infeed name, then a descriptive name
of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed.
Press Enter.
Example
The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the Switched CDU:
Switched CDU: set infeed name .aa HQ_1_Infeed_A