Server Technology Switched Rack PDU Installation And Operation Manual - page 59
Switched PDU
Installation and Operations Manual
Operations 59
Displaying outlets assigned to a group:
The List Group command displays outlets assigned to the specified group name.
To display outlets assigned to a group:
At the Switched CDU: prompt, type list group, followed by the group name and press Enter.
Example
The follow command displays the outlets assigned to the group ServerGroup_1:
Switched CDU: list group ServerGroup_1
Group: ServerGroup_1
Outlet Outlet
ID Name
.A1 DataServer_1
.A2 WebServer_1
.A3 FileServer_1
Displaying accessible serial ports:
The List Ports command displays accessible serial ports for the current user.
To display accessible serial ports:
At the Switched CDU: prompt, type list ports and press Enter.
Example
The follow command displays all accessible serial ports for the current user:
Switched CDU: list ports
Port Port
ID Name
Console Console
Displaying infeed status:
The Istat command displays the status of one or more infeeds.
This display includes the infeed absolute and descriptive names, as well as the Input Status and current Load reported
to the PDU by the infeed, branch or phase.
To display status of one or more infeeds:
Type istat and press Enter.
Examples
The following command displays the infeed status:
Switched CDU: istat
Input Input Input Input
Feed ID Feed Name Status Load
.AA Master On 10.5 Amps
Connecting to a serial device:
The Connect command allows Pass-Thru serial connection to devices attached to the standard serial port (Console).
To connect to a serial device:
At the Switched CDU: prompt, type connect console and press Enter.
NOTE: The Connect command will not immediately disconnect when issued from an SSH session that was established while another
Telnet or SSH session already existed.
To disconnect from a serial device:
Type !*break and press Enter.