Server Technology Switched Rack PDU Installation And Operation Manual - page 45
Switched PDU
Installation and Operations Manual
Operations 45
Configuring general parameters for any SNMP version:
Setting trap destinations:
Type an IP address or hostname as necessary in the trap destination field(s) and click Apply.
NOTE: Both IPv4 and IPv6 formats are accepted in the “Trap Destination 1” and “Trap Destination 2” fields.
Setting the error trap repeat time:
Type a time value in the Error Trap Repeat Time field and click Apply. The valid range is 1 to 65535 (in seconds).
Setting the trap format version:
The SNMP Trap Format configures the SNMP trap format version. The trap format can be SNMP v1, v2, or v3. The
default is v1, regardless of the versions that are enabled for the agent.
From the Trap Format drop-down menu, select the v1, v2, or v3 option and click Apply.
Setting IP restrictions:
From the IP Restrictions drop-down menu, select the No Restrictions or Trap Destinations Only option and click
Apply.
NOTE: When the Trap Destinations Only option is selected, SNMP Manager Get and Set requests are allowed only from the IP address of
the defined trap destinations.
Setting the SNMP SysName, SysLocation or SysContact objects:
In the appropriate field, enter the SysName, SysLocation or SysContact objects and click Apply.
Enabling or disabling tower traps:
Click on the Tower Traps link.
On the subsequent Tower Traps page, select or deselect the desired traps and click Apply.
Configuring input feed traps and thresholds:
Click on the Input Feed Traps and Thresholds link.
On the subsequent Input Feed Traps page, select or deselect the desired traps and click Apply.
For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and click Apply.
The default input feed high load threshold is 80% of the input feed maximum load capacity.
Configuring outlet traps:
Click on the Outlet Traps and Thresholds link.
On the subsequent Outlet Traps and Thresholds page, select or deselect the desired traps and click Apply.
Enabling or disabling Environmental Monitor traps:
Click on the Environmental Monitor Traps link.
On the subsequent page, select or deselect the desired traps and click Apply.
Configuring Temperature and Relative Humidity sensor traps:
Click the Sensor Traps and Thresholds link.
On the subsequent Sensor Traps and Thresholds page, select or deselect the desired trap checkboxes and click Apply.
Configuring Temperature and Relative Humidity sensor thresholds:
Click the Sensor Traps and Thresholds link.
For temperature thresholds, type a low and high temperature value in the Low Temp and High temp fields and click
Apply.
For relative humidity thresholds, type a low and high humidity percentage in the Low Humid and High Humid fields,
and click Apply.
NOTE: For temperature thresholds, the valid range is 0 to 123 in degrees Celsius or 32 to 254 in degrees Fahrenheit. For relative humidity,
the valid range is 0 to 100 (in percentage of relative humidity).