Server Technology Switched Rack PDU Installation And Operation Manual - page 68
68 Operations Switched PDU
Installation and Operations Manual
Setting the infeed operational voltage
The Set Infeed Voltage command is use to edit the input operational voltage.
To set the infeed operational voltage:
At the Switched CDU: prompt, type set infeed voltage, followed by the absolute infeed name, and a value from
1 to 480. Press Enter.
Example
The following commands sets the operational voltage for input .AA to 100V:
Switched CDU: set infeed voltage .aa 100
Setting the infeed maximum load capacity
The Set Infeed LoadMax command is use to edit the input maximum load capacity.
To set the infeed maximum load capacity:
At the Switched CDU: prompt, type set infeed loadmax, followed by the absolute infeed name, and a value from 1 to
255 (in amperes). Press Enter.
Example
The following commands sets the maximum load capacity for input .AA to 15 amperes:
Switched CDU: set infeed loadmax .aa 15
Displaying infeed information:
The Show Infeeds command displays information about all infeeds. This information includes the absolute and
descriptive infeed names, operational voltages and maximum load capacities.
To display tower information:
At the Switched CDU: prompt, type show infeeds and press Enter.
Example
Switched CDU: show infeeds
Input Input Input Input
Feed ID Feed Name Feed Voltage Feed Capacity (Amps)
.AA HQ_1_Infeed_A 100 15
.AB HQ_1_Infeed_B 120 20
.BA HQ_2_Infeed_A 120 30
.BB HQ_2_Infeed_B 120 30
Tower Administration
Creating a descriptive tower name:
The Set Tower Name command assigns a descriptive name to a tower. This descriptive name is displayed when the
Show Traps command is issued.
To create a tower name:
At the Switched CDU: prompt, type set tower name followed by the absolute tower name, then a descriptive name of
up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed.
Press Enter.
Example
The following command adds the descriptive name Florida_HQ_1 to tower .a:
Switched CDU: set tower name .a Florida_HQ_1
Setting the tower serial number:
The Set Tower ProdSN command is use to set the product serial number.
NOTE: If set at the factory, you cannot edit the serial number.