Server Technology Switched Rack PDU Installation And Operation Manual - page 112
112 Advanced Operations
Switched PDU
Installation and Operations Manual
Enabling or disabling a status trap:
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet.
To Enable or Disable a Status trap:
At the Switched CDU: prompt, type set trap (tower, infeed, outlet, em or ths) status, followed by the tower, infeed
or outlet name, and on or off.Press Enter, or\
Type set trap (tower, infeed, outlet, em or ths) Status all, followed by on or off and press Enter.
Examples
The following command enables the Status trap for the first tower, using the tower’s absolute name:
Switched CDU: set trap tower status .a on
The following command enables the Status trap for the tower named Florida_HQ_1:
Switched CDU: set trap tower status Florida_HQ_1 on
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet Status trap
automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is disabled, all associated Infeed
Status and Load and Outlet Status traps will be disabled.
Enabling or disabling a load trap:
The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.
To Enable or Disable a Load trap:
At the Switched CDU: prompt, type set trap infeed load, followed by the infeed name, and on or off.Press Enter, or
Type set trap infeed load all, followed by on or off and press Enter.
Examples
The following command enables the Load trap for second infeed on the first tower, using the absolute name of the
infeed:
Switched CDU: set trap infeed load .AB on
The following command disables the Load trap for all infeeds:
Switched CDU: set trap infeed load all off
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Infeed Load trap
automatically enables the Infeed and Tower Status traps for that infeed.
Setting the infeed load limit:
The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.
To set the infeed load limit:
At the Switched CDU: prompt, type set trap infeed loadhigh, followed by the infeed name, and a value from 0 to
255 in amperes. Press Enter.
Example
The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes, using the
absolute name of the infeed:
Switched CDU: set trap infeed loadhigh .ab 25