70 Operations Switched PDU
Installation and Operations Manual
Displaying tower information:
The Show Towers command displays information about the PDU. This information includes the absolute and
descriptive PDU names, serial and model numbers, and voltage types.
To display tower information:
At the Switched CDU: prompt, type show towers and press Enter.
Example
Switched CDU: show towers
Tower ID: .A
Name: TowerA
Product S/N: AA06F011157
Model No.: CW-8H1-C20
3-Phase: No
Power Type: AC
More (Y/es N/o):
Group Administration
Creating a group name:
The Create Group command creates a new group name.
To create a group name:
At the Switched CDU: prompt, type create group optionally followed by a descriptive name of up to 24 alphanumeric
and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Group names are not case
sensitive. Press Enter.
Example
The following command creates group name ServerGroup_1:
Switched CDU: create group ServerGroup_1
Removing a group name:
The Remove Group command removes a group name.
To remove a group name:
At the Switched CDU: prompt, type remove group, optionally followed by a username. Press Enter.
Example
The following command removes group name ServerGroup_1: