Server Technology Switched Rack PDU Installation And Operation Manual - page 146
146 Advanced Operations
Switched PDU
Installation and Operations Manual
Setting the shutdown script delay:
The Set Outlet Script Delay command sets the shutdown script delay for an outlet.
To set the shutdown script delay:
At the Switched CDU: prompt, type set outlet script delay, followed by the outlet ID, and a value from 1 to 15 (in
minutes). Press Enter.
Example
The following command sets the shutdown script delay for outlet .a1 to 10 minutes:
Switched CDU: set outlet shutdown delay .a1 10
Displaying Remote Shutdown information:
The Show Shutdown command displays all shutdown configuration information.
Outlet ID and descriptive name
Remote Shutdown settings
Shutdown script setting
To display shutdown information:
At the Switched CDU: prompt, type show shutdown and press Enter.
Example
The following command displays all shutdown information:
Switched CDU: show shutdown
Outlet Outlet Name & Shutdown/ Script/
ID Hostname/IP Delay (sec) Delay (min)
.A1 DataServer_1 Yes /90 Yes /10
Windows2003
.A2 WebServer_1 No /120 No /1
.A3 FileServer_1 No /90 No /1
.A4 TowerA_Outlet4 No /90 No /1
.A5 TowerA_Outlet5 No /90 No /1
.A6 TowerA_Outlet6 No /90 No /1
.A7 TowerA_Outlet7 No /90 No /1