Server Technology Switched Rack PDU Installation And Operation Manual - page 145
Switched PDU
Installation and Operations Manual
Advanced Operations 145
Enabling and Setting up Remote Shutdown Support
Remote Shutdown Command Summary
Command
Description
Set Outlet Host
Sets the target server Host IP address or hostname
Set Outlet Shutdown
Enables or Disables Remote Shutdown
Set Outlet Shutdown Delay
Sets the outlet Remote Shutdown delay
Set Outlet Script
Enables or disables shutdown script delays
Set Outlet Script Delay
Sets the outlet shutdown script delay
Show Shutdown
Displays Remote Shutdown configuration information
Enabling or disabling Remote Shutdown support:
The Set Outlet Shutdown command enables or disables Remote Shutdown support for an outlet.
To enable or disable Remote Shutdown support:
At the Switched CDU: prompt, type set outlet shutdown, followed by yes or no, and the outlet ID. Press Enter.
Example
The following command enables Remote Shutdown from outlet .a1:
Switched CDU: set outlet shutdown yes .a1
Setting the Remote Shutdown delay:
The Set Outlet Shutdown Delay command sets the Remote Shutdown delay for an outlet.
To set the Remote Shutdown delay:
At the Switched CDU: prompt, type set outlet shutdown delay, followed by the outlet ID, and a value from 1 to 900
(in seconds). Press Enter.
Example
The following command sets the Remote Shutdown delay for outlet .a2 to 120 seconds:
Switched CDU: set outlet shutdown delay .a2 120
Setting the outlet host address:
The Set Outlet Host command set the IP address or hostname for an outlet. Hostnames can be up to 60 characters
long.
To set the outlet host address:
At the Switched CDU: prompt, type set outlet host, followed by the outlet ID, and the IP address or hostname. Press
Enter.
Example
The following command set the hostname for outlet .a1 to ‘Windows2003’:
Switched CDU: set outlet host .a1 Windows2003
Enabling or disabling shutdown script support:
The Set Outlet Script command enables or disables shutdown script support for an outlet.
To enable or disable shutdown script support:
At the Switched CDU: prompt, type set outlet script, followed by yes or no, and the outlet ID. Press Enter.
Example
The following command enables Remote Shutdown from outlet .a1:
Switched CDU: set outlet script yes .a1