Server Technology Switched Rack PDU Installation And Operation Manual - page 57
Switched PDU
Installation and Operations Manual
Operations 57
Turning outlets off:
The Off command turns off one or more outlets. When the command completes, a display indicating all outlets
affected and their current states will be displayed.
To turn outlets off:
At the Switched CDU: prompt, type off, followed by an outlet name, and press Enter, or
Type off, followed by a group name, and press Enter, or
Type off all and press Enter
Examples
The following command turns off the outlet named FileServer_1:
Switched CDU: off FileServer_1
The following command turns off all outlets:
Switched CDU: off all
Rebooting outlets:
The Reboot command reboots one or more outlets. This operation turns the outlet(s) off, delays for a user
configurable period and then turns the outlet(s) on. When the command completes, a display indicating all outlets
affected and their current states will be displayed.
NOTE: You will have to reissue the Status command to verify that the outlets have rebooted.
To reboot one or more outlets:
At the Switched CDU: prompt, type reboot, followed by an outlet name, and press Enter, or
Type reboot, followed by a group name, and press Enter, or
Type reboot all and press Enter.
Example
The following command reboots all the outlets in the group named ServerGroup_1:
Switched CDU: reboot ServerGroup_1
Displaying outlet status:
The Status command displays the on/off status of one or more outlets. The command displays the status of only those outlets
for which the current username has power control access.
This display includes the outlet absolute and descriptive names, the Outlet State reported to the unit by the outlet and
the current Control State being applied by the firmware. If you do not specify any parameter with this command, the
status of all accessible outlets is displayed.
NOTE: If you have access to more than 16 total outlets, the Status command displays the first 16 outlets with a prompt to allow you to view
the remaining outlets.