ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 101
• send "1" at crossing lower: Should current threshold 1 be
undershot, the value 1 is sent via the communication object
Status Current-Threshold 1
. With an undershoot the value 0 is set
but no telegram is sent.
• send "0" at crossing over - "1" at crossing lower: Should current
threshold 1 be overshot, the value 0 is sent via the
communication object Status Current-Threshold 1; with an
undershoot the value 1.
• send "1" at crossing over - "0" at crossing lower: Should current
threshold 1 be overshot, the value 1 is sent via the
communication object Status Current-Threshold 1; with an
undershoot the value 0.
The sending of the status occurs after the evaluation delay at the
earliest and only when the status has changed.
Enable current threshold 2
Options: no
yes
With this parameter, the second current threshold and the respective
communication object Status Current-Threshold 2 are enabled. For Status
Current-Threshold 2
, the same evaluation delay and scaling and the same
evaluation properties as for Threshold 1 apply.
yes: The following parameter appears:
Current threshold 2 in mA
(scaled in 10 mA or 100 mA)
Value of hysteresis current threshold 2
Current threshold 2 +/- hysteresis
The setting options of this parameter do not differentiate from the
current threshold 1. The descriptions of the parameters can be found
further above in this chapter.
Enable "Safety Priority x"
See product manual for further instructions