ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 77
Flashing if object "Switching" is
Options: ON
(1)
OFF
(0)
ON (1) or OFF (0)
Here you set the value of the communication object Switch at which the
output flashes. Flashing is not retriggerable.
ON (1): Flashing starts when a telegram with the value 1 is received on
the communication object Switch.
A telegram with the value 0 ends flashing.
OFF (0): Flashing starts when a telegram with the value 0 is received on
the communication object Switch.
A telegram with the value 1 ends flashing.
ON (1) or OFF (0): A telegram with the value 1 or 0 triggers flashing.
Suspension of flashing is not possible in this case.
Time for ON: Min. [0…65,535]
Time for ON: Sec. [0…59]
Options: 0…65,535
1…5…59
This time for ON defines how long the output is switched ON during a
flashing period. The smallest value is 1 second.
Note
Only a certain number of switching actions are possible per minute and
Switch Actuator. With frequent switching, a switching delay can occur, as
only a certain number of switching actions are possible per minute, see
, from page 7. The same applies directly after bus voltage
recovery.
Time for OFF: Min. [0…65,535]
Time for OFF: Sec. [0…59]
Options: 0…65,535
1…5…59
This time for OFF defines how long the output is switched ON during a
flashing period. The smallest value is 1 second.
Note
Only a certain number of switching actions are possible per minute and
Switch Actuator. With frequent switching, a switching delay can occur, as
only a certain number of switching actions are possible per minute, see
, from page 7. The same applies directly after bus voltage
recovery.