ABB SA/S 12.16.6.1 Product Manual - Knx Device
ABB i-bus
®
KNX Device
technology
14 2CDC 505 056 D0207 | SA/S
2.2.2
Output lamp load 10 A
Lamps
Incandescent lamp load
2500 W
Fluorescent lamps T5 / T8
Uncorrected
Parallel compensated
DUO circuit
2500 W
1500 W
1500 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
1200 W
1500 W
Halogen lamps 230 V
2500 W
Dulux lamp
Uncorrected
Parallel compensated
1100 W
1100 W
Mercury-vapour lamp
Uncorrected
Parallel compensated
2000 W
2000 W
Switching performance (switching
contact)
Maximum peak inrush-current I
p
(150
μs) 400
A
Maximum peak inrush-current I
p
(250
μs) 320
A
Maximum peak inrush-current I
p
(600
μs) 200
A
Number of electronic ballasts (T5/T8,
single element)
1)
18 W (ABB EVG 1 x 18 SF)
23
24 W (ABB EVG-T5 1 x 24 CY)
23
36 W (ABB EVG 1 x 36 CF)
14
58 W (ABB EVG 1 x 58 CF)
11
80 W (Helvar EL 1 x 80 SC)
10
1)
For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the electronic ballasts,
see
, page 35.
Device type
Application program
Maximum number of
communication objects
Maximum number of
group addresses
Maximum number of
associations
SA/S 2.10.1
Switch 2f 10A/…*
34 254 254
SA/S 4.10.1
Switch 4f 10A/…*
64
254
254
SA/S 8.10.1
Switch 8f 10A/…*
124 254 254
SA/S 12.10.1
Switch 12f 10A/…*
184
254
254
* … = current version number of the application program
Note
The ETS and the current version of the device application program are
required for programming.
The current version of the application program is available for download
on the Internet at www.abb.com/knx. After import it is available in the ETS
under ABB/Output/Binary output xf 10A/…* (x = 2, 4, 8 or 12).
The device does not support the closing function of a KNX device in the
ETS. If you inhibit access to all devices of the project with a BCU code, it