ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
58 2CDC 505 056 D0207 | SA/S
Control period in seconds
(0…65,535s, 0 = inactive)
Options: 0…65,535
This parameter defines the control period of the function Safety
Priority x
. If a telegram is received in this time with the defined
triggering condition as defined in parameter Function Safety Priority x,
on communication object Safety Priority x*, it will be triggered. Should
the communication object Safety Priority x* receive a telegram that
does not fulfil the trigger conditions, the control period is reset and
restarted.
0: There is no monitoring. However, the Safety Priority x is triggered
when a telegram with the defined triggering condition, as defined in
parameter Function Safety Priority x, on communication object Safety
Priority x*
is received.
*x = 1, 2 or 3
Note
The control period in the Switch Actuator should be at least twice as
long as the cyclical transmission time of the sensor, so that the
immediate absence of a signal, e.g. due to a high bus load, does
not immediately result in an alarm.