ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 113
Note
The function current detection and the respective parameter window are
only visible with the Switch Actuators with current detection (SA/S
x.16.6.1). They are both equally available in the Switch Actuator and
Heating Actuator
modes.
Status response of switching state
Object "Status Switch"
Options: no
after a change
always
This parameter can enable the communication object Status Switch. This
contains the current switching state and the present contact position.
• no: The switch state is updated but the status is not actively sent on
the bus.
• after a change: With a change of the switch state, the status is
actively sent on the bus via the communication object Status Switch.
This can have a major affect on the bus load on a Switch Actuator
with several outputs.
• always: The status of the switch state is always actively sent on the
bus via the communication object Status Switch, even when a change
in status has not occurred. Transmission is triggered as soon as the
communication objects Control value or Valve purge receive a
telegram.
Note
With a change of the parameterization or after a subsequent switching of
the status object, the assignment of the group addresses already
allocated to the Switch communication object is lost and needs to be
reprogrammed.