ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
76 2CDC 505 056 D0207 | SA/S
The following parameter appears with the selection Flashing:
The output starts to flash as soon as the parameterized value is received in
the communication object Switch. The flashing period can be adjusted via
the parameterized time duration for ON or OFF. At the start of the flashing
period, the output is switched on with a normally open contact and off with a
normally closed contact. When a new value is received on the
communication object Switch, the flashing period will recommence.
The relay state after flashing can be programmed.
Flashing can be inverted when the output is used as a normally closed
contact.
The communication object Status switch indicates the current relay state
during flashing.
Note
Only a certain number of switching actions are possible per minute and
Switch Actuator. With frequent switching, a switching delay can occur, as
only a certain number of switching actions are possible per minute, see
, from page 7. The same applies directly after bus voltage
recovery.
When the function Flashing is selected, the service life of the switching
contacts must be considered, see
With a telegram to the communication object Disable time function, the
function Flashing can be disabled. The parameterization is undertaken in
parameter window
, page 64, with the parameter Value object
"Disable Time Function" after bus voltage recovery
.