ABB SA/S 12.16.6.1 Product Manual - Knx Device
ABB i-bus
®
KNX Device
technology
SA/S | 2CDC 505 056 D0207 29
Ambient conditions
Maximum air humidity
93 %, no condensation allowed
Design
Modular installation device (MDRC)
Modular installation device, ProM
SA/S type
2.16.6.1 4.16.6.1 8.16.6.1 12.16.6.1
Dimensions
90 x W x 64.5 mm (H x W x D)
Width W in mm
36 72 144 216
Mounting width in space units (18 mm unit)
2 4 8 12
Mounting depth in mm
64.5 64.5 64.5 64.5
Weight
in kg
0.2 0.34 0.64 0.83
Installation
On 35 mm mounting rail
To EN 60 715
Mounting position
As required
Housing/colour
Plastic housing, grey
Approvals
KNX to EN 50 090-1, -2
Certification
CE mark
In accordance with the EMC guideline and
low voltage guideline
1)
Further information concerning electrical endurance to IEC 60 947-4-1 can be found at:
AC1-, AC3-, AX-, C-Load specifications
2)
The maximum peak inrush current may not be exceeded.
3)
The specifications apply only after the bus voltage has been applied to the device for at least 30 seconds. Typical response delay of the relay is approx. 20 ms.
2.5.2
Output lamp load 16/20 A
Lamps
Incandescent lamp load
3680 W
Fluorescent lamps T5 / T8
Uncorrected
Parallel compensated
DUO circuit
3680 W
2500 W
3680 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
2000 W
2500 W
Halogen lamps 230 V
3680 W
Dulux lamp
Uncorrected
Parallel compensated
3680 W
3000 W
Mercury-vapour lamp
Uncorrected
Parallel compensated
3680 W
3680 W
Switching performance (switch contact)
Maximum peak inrush-current I
p
(150
μs) 600
A
Maximum peak inrush-current I
p
(250
μs) 480
A
Maximum peak inrush-current I
p
(600
μs) 300
A
Number of electronic ballasts (T5/T8,
single element)
1)
18 W (ABB EVG 1 x 18 SF)
26
2)
24 W (ABB EVG-T5 1 x 24 CY)
26
2)
36 W (ABB EVG 1 x 36 CF)
22
58 W (ABB EVG 1 x 58 CF)
12
2)
80 W (Helvar EL 1 x 80 SC)
10
2)
1)
For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the electronic ballasts,
2)
The number of ballasts is limited by the protection with B16 circuit-breakers.