ABB SA/S 12.16.6.1 Product Manual - Knx Device
ABB i-bus
®
KNX Device
technology
SA/S | 2CDC 505 056 D0207 23
Output switching times
3)
Maximum relay position change of output and
minute if all relays are switched
simultaneously.
The position changes should be distributed
equally within the minute.
2.16.5.1 4.16.5.1 8.16.5.1 12.16.5.1
30 15 7 5
Maximum relay position change per
output and minute if only one relay is
switched.
60 60 60 60
Connections
KNX
Via bus connection terminals
0.8 mm Ø, solid
Load current circuits (2 terminal per relay)
Universal head screw terminal (PZ 1)
0.2…4 mm
2
stranded, 2 x 0.2…2.5 mm
2
0.2…6 mm
2
solid, 2 x 0.2…4 mm
2
Ferrules without/with plastic sleeves
0.25…2.5/4 mm
2
TWIN ferrules
0.5…2.5 mm
2
Contact pin length at least 10 mm
Tightening torque
Maximum 0.8 Nm
Operating and display elements
Programming button/LED
For assignment of the physical address
Switch position display
Relay operator
Enclosure
IP 20
To EN 60 529
Safety class
II
To EN 61 140
Isolation category
Overvoltage category
III to EN 60 664-1
Pollution degree
2 to EN 60 664-1
KNX safety extra low voltage
SELV 24 V DC
Temperature range
Operation
Storage
Transport
-5 °C…+45 °C
-25 °C…+55 °C
-25 °C…+70 °C
Ambient conditions
Maximum air humidity
93 %, no condensation allowed
Design
Modular installation device (MDRC)
2.16.5.1 4.16.5.1 8.16.5.1
12.16.5.1
Dimensions
90 x W x 64.5 mm (H x W x D)
Width W in mm
36 72 144 216
Mounting width in space units (modules at 18
mm)
2 4 8 12
Mounting depth in mm
64.5 64.5 64.5 64.5
Weight
in kg
0.2 0.34 0.64 0.75
Installation
On 35 mm mounting rail
To EN 60 715
Mounting position
As required
Housing/colour
Plastic housing, grey
Approvals
KNX to EN 50 090-1, -2
Certification
CE mark
In accordance with the EMC guideline and
low voltage guideline
1)
Further information concerning electrical endurance to IEC 60 947-4-1 can be found at:
AC1-, AC3-, AX-, C-Load specifications
2)
The maximum peak inrush current may not be exceeded.
3)
The specifications apply only after the bus voltage has been applied to the device for at least 30 seconds. Typical response delay of the relay is approx. 20 ms.