ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 57
Enable Safety Object for operating mode
"Switch Actuator"
Options: no
yes
yes: Three further parameters appear:
Function Safety Priority 1
Function Safety Priority 2
Function Safety Priority 3
Options: inactive
Is triggered by object value “0”
Is triggered by object value “1”
Note
The functions and setting options of the parameter Function Safety Priority
2
and Function Safety Priority 3 do not differentiate from those of
parameter Function Safety Priority 1.
In Switch Actuator mode, there are three Function Safety Priority x*
parameters available. For every priority, your own trigger condition (safety
disconnection) can be defined here. With safety disconnection, 1
communication object Safety Priority x* becomes visible each time. These
communication objects relate to the entire device. However, every output
can react differently to the receipt of a telegram. The reaction of the output is
parameterised in the parameter window X: Safety of the corresponding
output.
*x = 1, 2 or 3
inactive: The function Safety Priority x is not used.
Is triggered by object value “0”: Activation of the safety is triggered if at
communication object Safety Priority x* a telegram with the value 0 is
received. The following parameter appears.
Is triggered by object value "1": Activation of the safety is triggered if at
communication object Safety Priority x* a telegram with the value 1 is
received. The following parameter appears: