ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 49
3.1.1.1.1 Conversion summary
All
applications
Switch.../3.1
or 3.2 (SA/S x.16.y.1 with or without current
detection) are mutually convertible.
The
applications
Switch...CS/2.0
(SA/S x.16.5S with current detection!)
are permissible as a source.
The
application
Switch 12f 16C/2.0
(SA/S 12.16.5 12-fold device without
current detection) is not possible as a source.
The general rules covering conversion apply (parameters in the source
device, which do not exist in the target device, are ignored. Parameters
in the target device, which do not exist in the source device, receive their
default value).
3.1.1.2
Procedure
Import the current VD3 file into ETS3 and add a product with the current
application program to the project.
After you have parameterized a device, you can transfer the settings to a
second device.
Right click on the product and select Convert.
Subsequently, the required settings are undertaken in the dialog.
Finally, exchange the physical address and delete the old device.
Should you wish to only copy individual channels within a device, use the