28
Status Current-Threshold 2
Output A
EIS 1, 1 bit
DPT 1.002
C, R, T
This communication object is enabled if in parameter window A: Current Detection
the parameter Enable current threshold value(s) and the parameter Enable current threshold 2
has been selected with the option yes.
The status of the current threshold 1 is only sent when a change occurs.
The status value can be inverted.
Telegram value
1 = threshold 2 plus threshold 2 hysteresis is exceeded
0 = threshold 2 minus threshold 2 hysteresis is
exceeded
For further information see:
Function thershold with current detection
29
Status Switch
Output A
EIS 1, 1 bit
DPT 1.001
C, R, T
This communication object is enabled if in parameter window A: General
the parameter Status response of switching state Object "Status Switch" or the option always
have been selected.
The communication object value directly indicates the current contact position of the switching
relay.
The status value can be inverted.
Telegram value
1 = relay ON or OFF depending on the parameterization
0 = relay OFF or ON depending on the parameterization