ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 71
The following parameter appears with the selection Staircase lighting:
Duration of staircase lighting
Minutes (0...1000)
Options: 0…5…1,000
Seconds
Options: 0…59
The staircase lighting time defines how long the contact is closed –
provided that the contact is programmed as a normally open contact –
and how long the light remains on after an ON telegram. The input is
made in minutes and seconds. The staircase lighting time may extend
depending on the value set in the parameter Warning before end of
staircase lighting
.
Extending staircase lighting by multiple
operation (“pumping up”)
Options:
no (not retriggerable)
yes
(retriggerable)
up to max. 2x staircase lighting time
up to max. 3x staircase lighting time
up to max. 4x staircase lighting time
up to max. 5x staircase lighting time
If a further ON telegram is received during the staircase lighting time
sequence, the remaining staircase lighting time can be extended by a
further period. This is possible by repeated operation of the push
button (“pumping up“) until the maximum programmed number of
retriggering operations is reached. The maximum time can be set to
1, 2, 3, 4 or 5-fold time of the staircase lighting time.
The staircase lighting time is extended by “pumping up” to the
maximum time. If some of the time has already timed out, the
staircase lighting time can again be extended to the maximum time by
“pumping up”.
The parameterised maximum time may not however be exceeded.
no: The receipt of an ON telegram is ignored.
Die Treppenlichtzeit läuft unverändert zu Ende.
yes (retriggerable): The staircase light time is reset each time by a
renewed ON telegram and starts to count again each time. This process
can be repeated as often as desired using this selection.
• Up to max. 2/3/4/5 x staircase lighting time: The staircase lighting
time is extended by the 2/3/4/5-fold staircase lighting time with a
renewed ON telegram.