64 2CDC 505 056 D0207 | SA/S
3.2.3.1
Parameter window
A: Function
In this parameter window, you determine the behaviour of the output and
can enable different functions, where further parameters windows become
available.
Reaction of output
Options:
Normally closed contact
Normally open contact
This parameter determines the behaviour of the output as a normally open
or normally closed contact.
Normally closed contact: An ON telegram (1) opens the contact and an
OFF telegram (0) closes the contact.
Normally open: An ON telegram (1) closes the contact and an OFF
telegram (0) opens the contact.
Enable time functions: "delay, staircase lighting, flashing"
Options: no
yes
no: The parameter window A: Time for output A is not enabled.
yes: The parameter window A: Time for output A as well as the
communication object Time function disable is enabled.
Using this communication object, the function Time can be enabled
(telegram with value 0) or disabled (telegram with value 1) via the bus.
As long as the function Time is disabled, the output can only be switched on
and off without delay via the communication object Switch.
The priorities as listed in