ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
128 2CDC 505 056 D0207 | SA/S
3.2.6.2
Communication objects
Output A
Note
In this product manual, all the current 2/4/8 and 12-fold Switch Actuators
are described. These devices each have 2/4/8 or 12 outputs. However, as
the functions for all outputs are identical, only the functions of output A will
be described.
Should the details in the product manual refer to all outputs, 2-fold
corresponds to outputs A…B, 4-fold corresponds to outputs A…D, 8-fold
corresponds to outputs A…H and 12-fold corresponds to outputs A…L;
the designation outputs A…X is used.
The variants with current detection feature an additional parameter page
as well as additional communication objects for this function.
The descriptions of the parameter setting options of Outputs A…X are
described from parameter window
No.
Function
Object name
Data type
Flags
10
Switch
Output A
EIS 1, 1 bit
DPT 1.001
C, W
This communication object is visible if the control of the heating actuator is implemented via a
1 bit communication object. The heating valve is controlled directly using it.
The device receives a switch telegram via the switch object.
Normally open:
Telegram value
1 = valve open
0 = valve closed
Normally closed contact:
Telegram value
1 = valve closed
0 = valve open
10
Control value (PWM)
Output A
EIS 6, 1 byte
DPT 5.010
C, W
This communication object is visible if the control of the heating actuator is implemented via a
1 bit communication object, e.g. within a continuous control. The communication object value
(0…255) is determined by the variable mark-to-space ratio of the valve.
Telegram value
1 = valve closed
0 = valve open