ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
106 2CDC 505 056 D0207 | SA/S
No.
Function
Object name
Data type
Flags
12
Disable time function
Output A
EIS 1, 1 bit
DPT 1.003
C, W
This communication object is enabled if in parameter window A: Function
the parameter Enable function time has been selected with the option yes.
After bus voltage recovery, in the parameter window A: Function the communication object
value with the parameter Value object "Disable Time Function" on bus voltage recovery can be
determined, for example see:
With the blocked function Time, the output can only be switched on or off, Enable time
functions "delay, staircase lighting, flashing"
is not triggered.
Telegram value
1 = Disable function time
0 = Function time enabled
The contact position at the time of disabling and enabling is retained and will only be changed
with the next switch telegram to the communication object Switch.
13
Duration of staircase
lighting
Output A
EIS 10, 2 byte
DPT 7.005
C, R, W
This communication object is enabled if in parameter window A: Time
the parameter Duration of staircase lighting can be changed by object has been selected with
the option yes.
The duration of staircase lighting is set here. The time is defined in seconds.
After bus voltage recovery, the value of the communication object is set by the programmed
value and the value set via the bus is overwritten.
14
Warning stair lighting
Output A
EIS 1, 1 bit
DPT 1.005
C, T
This communication object is enabled if in parameter window A: Time
the function staircase light and in parameter Warning before end of staircase lighting the
option via object or via object and switching ON/OFF have been selected.
15
Call preset 1/2
Output A
EIS 1, 1 bit
DPT 1.022
C, W
This communication object is enabled if in parameter window A: Function
the parameter Enable function "presets" has been selected with the option yes.
Via this communication object, a stored switch state is recalled.
It is possible with the corresponding parameterization through a recall of Preset 1/2 to restore
the switching state before the recall of Preset 2 or to reset the switching state to the
parameterised value before Preset 2.
Telegram value
0 = The parameterised value (switch state) of Preset 1 is
recalled.
1 = The parameterised value (switch state) of Preset 2 is recalled.
For further information see:
, page 147