ABB i-bus
®
KNX Commissioning
122 2CDC 505 056 D0207 | SA/S
3.2.5.1.2 Parameter window
A: Forced Operation
In this parameter window, all settings for the function Forced operation are
undertaken.
This parameter is visible if in parameter window
, page 117, the
parameter Function forced operation has been enabled.
During a forced operation, the Switch Actuator triggers a freely adjustable
forced position. This has the highest priority, i.e. it is not modified by a valve
purge or safety position.
The forced operation (positioning) can be activated via the communication
object Forced operation = "1" and deactivated via the communication object
Forced operation = "0"
.
Valve position during forced positioning
Options: unchanged
0%
(closed)
10%
(26)
...
90%
(230)
100%
(open)
The valve position triggered by the actuator during the forced operation is
determined by this parameter. The values in brackets correspond to a 1 byte
value.
The switch cycle time t
CYC
used for control is to be programmed in the
parameter cycle time for continuous control in parameter window A: General.
At the end of forced operation, the Switch Actuator returns to its normal
method of operation and calculates its next switch state value from the
incoming values on communication objects Switch or Control value (PWM).