ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 97
Enable current threshold value(s)
Options: no
yes
Up to two current thresholds for detected currents can be enabled.
no: No current threshold values can be enabled.
yes: First of all, a current threshold value with the respective
parameterization option and the communication object Status Current-
Threshold 1
are enabled.
The following parameters appear:
Evaluation
Options: always
only with a closed contact
only with an opened contact
This parameter determines the contact position at which the
information Threshold undershoot or Threshold overshoot is sent.
• always: An overshoot or undershoot of the set current threshold is
detected at every contact position.
This is only sent on the KNX should the status change.
As a result, by a contact opened via the KNX (current flow
interrupted), a current threshold undershoot (as error) is always
detected. This is however only sent with a status change.