ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 95
Datapoint type object "Current Value"
(0...65,535 in mA)
Options:
2 byte counter (DTP 7.012)
4 byte float (DTP 14.019)
This parameter determines the data type (datapoint, DTP) of the
communication object Current Value. A 2 byte counter (EIS 10, DPT 7.012,
1 mA per digit) or a 4 byte float value (EIS 9, DTP 14.019) can be selected.
Note
The current detection range is designed for currents between 20 mA and
20 A.
Send current value, transmission time
(0...65,535s, 0 = not send)
Options:
0
1…65,535
This parameter determines if and at which intervals the present value of
current is sent via the communication object Current Value.
The cycle time must be entered in seconds.
0: No current values are sent cyclically via the bus.
The present current values are however continuously available in the
communication object Current Value of the output and can be read out.
Send current value on change of value
Options:
no
25/50/100/200/500 mA
1/2/5 A
This parameter determines that with a load change the current value is sent
via the communication object Current Value on the bus. A current value is
always sent on the bus if the current change is greater than the current value
set in this parameter. The current value sent on the bus only applies as a
new reference value.
no: No current value is sent.
The smaller the set current value, the more precisely the sent current value
will correspond with the actual current value. With a highly fluctuating current
value, a high bus load may occur.
For further information see: