ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
130 2CDC 505 056 D0207 | SA/S
No.
Function
Object name
Data type
Flags
15
Status heating
Output A
EIS 6, 1 byte
DPT 5.010
C, T
This communication object is visible if the control of the heating actuator is implemented via a
1 bit communication object, e.g. within a continuous control, and the feedback of the control
value is parameterised with a 1 byte value.
The current 1 byte control value of the output is sent via this communication object.
15
Status heating
Output A
EIS 1, 1 bit
DPT 1.001
C, T
This communication object is visible if the control of the heating actuator is implemented via a
1 bit communication object, e.g. within a continuous control, and the feedback of the control
value is parameterised with a 1 bit value.
The current 1 bit control value of the output is sent on a change via this communication object.
With the selection of the option 0% = "0" otherwise "1", the following applies:
Telegram value:
1 = control value is not equal to 0 %
0 = control value is equal to 0 %
With the selection of the option 0% = "1" otherwise "0", the following applies:
Telegram value:
1 = control value is equal to 0 %
0 = control value is not equal to 0 %
16…
24
Not assigned.
25
Contact monitoring
Output A
EIS 1, 1 bit
DPT 1.002
C, R, T
This communication object is enabled if in parameter window A: Function
the parameter Enable function "current detection" has been selected with the option yes.
The communication object value shows the contact state when the contact is open.
Should a current flow be detected with an opening of the contact initiated via the KNX, contact
welding or manual switch on has occurred (contact fault). The evaluation of whether a current
flows occurs about one second after a contact is opened. The current is safely detected
should a measurable current (about 20 mA) flow. A prerequisite for correct evaluation is
switching via the KNX.
Telegram value
1 = contact error
0 = no current flows