ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 105
No.
Function
Object name
Data type
Flags
10
Switch
Output A
EIS 1, 1 bit
DPT 1.001
C, W
This communication object is used for switching of the output ON/OFF.
The device receives a switch telegram via the switch object.
Normally open:
Telegram value
1 = switch ON
0 = switch OFF
Normally closed contact:
Telegram value
1 = switch OFF
0 = switch ON
Note
With logical connections or forced operations, a modification of the Switch
communication object does not necessarily lead to a change of the contact
position.
For further information see:
11
Permanent ON
Output A
EIS 1, 1 bit
DPT 1.001
C, W
This communication object is enabled if in parameter window A: Function
the parameter Enable function time has been selected with the option yes.
With this communication object, the output can be forcibly switched on.
If the communication object is assigned with the value 1, the output is switched on irrespective
of the value of the object Switch and remains switched on until the communication object
Permanent ON
has the value 0. After ending the permanent ON state, the state of the
communication object Switch is used.
Permanent ON
only switches ON and “masks” the other functions. This means that the other
functions, e.g. staircase lighting, continue to run in the background but do not initiate a
switching action. After the end of permanent ON, the switching state that would result without
the permanent ON function becomes active. The behaviour for the function staircase lighting
after Permanent ON is programmed in parameter window
This communication object can be used for example to allow the service or maintenance and
cleaning personnel to initiate a permanent ON. The device receives a switch telegram via the
switch object.
Permanent On
becomes inactive after a download or bus voltage recovery.
Telegram value
1 = activates permanent ON mode
0 = deactivates permanent ON mode