ABB SA/S 12.16.6.1 Product Manual - Knx Device
ABB i-bus
®
KNX Device
technology
24 2CDC 505 056 D0207 | SA/S
2.4.2
Output
lamp load 16/20 A
Lamps
Incandescent lamp load
3680W
Fluorescent lamps T5 / T8
Uncorrected
Parallel compensated
DUO circuit
3680W
2500W
3680W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
2000 W
2500W
Halogen lamps 230 V
3680W
Dulux lamp
Uncorrected
Parallel compensated
3680W
3000W
Mercury-vapour lamp
Uncorrected
Parallel compensated
3680W
3680W
Switching performance (switch contact)
Maximum peak inrush-current I
p
(150
μs) 600A
Maximum peak inrush-current I
p
(250
μs) 480A
Maximum peak inrush-current I
p
(600
μs) 300A
18 W (ABB EVG 1 x 18 SF)
26
2)
Number of electronic ballasts (T5/T8,
single element)
1)
24 W (ABB EVG-T5 1 x 24 CY)
26
2)
36 W (ABB EVG 1 x 36 CF)
22
58 W (ABB EVG 1 x 58 CF)
12
2)
80 W (Helvar EL 1 x 80 SC)
10
2)
1)
For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the electronic ballasts,
see
, page 35.
2)
The number of ballasts is limited by the protection with B16 circuit-breakers.
Device type
Application program
Maximum number of
communication objects
Maximum number of
group addresses
Maximum number of
associations
SA/S 2.16.5.1
Switch 2f 16C/…*
34 254 254
SA/S 4.16.5.1
Switch 4f 16C/…*
64
254
254
SA/S 8.16.5.1
Switch 8f 16C/…*
124 254 254
SA/S 12.16.5.1
Switch 12f 16C/…*
184
254
254
* … = current version number of the application program
Note
The ETS and the current version of the device application program are
required for programming.
The current version of the application program is available for download
on the Internet at www.abb.com/knx. After import it is available in the ETS
under ABB/Output/Binary output xf 16C/…* (x = 2, 4, 8 or 12).
The device does not support the closing function of a KNX device in the
ETS. If you inhibit access to all devices of the project with a BCU code, it
has no effect on this device. Data can still be read and programmed.