ABB SA/S 12.16.6.1 Product Manual - Knx Commissioning
Manual is about: Switch Actuators
of
172
ABB i-bus
®
KNX Commissioning
SA/S | 2CDC 505 056 D0207 121
Position of the valve drive during
fault of room thermostat
Options: unchanged
0%
(closed)
10%
(26)
...
90%
(230)
100%
(open)
This parameter determines the safety position that is controlled in error
mode by the SA/S. The values in brackets correspond to a 1 byte value.
The switch cycle time t
CYC
used for control is to be programmed in the
parameter cycle time for continuous control in parameter window A: General.
Enable object "RTR fault"
Options: no
yes
Using this parameter, the communication object Fault control value can
be enabled. During fault mode, the communication object has the value 1,
if there is no fault the value is 0.