Server Technology switched pro2 User Manual - page 125
Switched PRO2 – User Guide
Using the Web Interface
•
125
Restart Options for the PRO2:
Note: PRO2 products support unit persistence. This means that if a link unit is connected to a master unit, and
the link unit
is disconnected (powered down or accidentally disconnected), and the master unit is restarted, the link unit will be reported
as “Not Found” after the restart because the link unit is no longer physically connected to the master.
However, the association between the master/link units is retained to allow the continuation of alerts. If the disconnected
link unit is physically re-
connected to the master, the “Not Found” status will return to “Normal” status.
To intentionally remove a link unit from connection with a master unit, the link unit must be purged using the Purge function.
Unit persistence affects all connected PRO2 master/link units whether or not they are connected in a multi-linking
configuration.
This restart option…
performs this action on the PRO2
…
Restart
Performs a warm boot; system user/outlet/outlet group configuration settings and outlet
states are not changed or reset with the restart command.
Restart and reset to factory
defaults
Resets the non-volatile RAM where configuration values are stored. This option clears
all administrator-editabled fields and resets all CLI configurable options to their factory
default values, including all user accounts.
Resetting the PRO2 to factory default values also resets all TCP/IP and Telnet/Web
configurations. Reconfiguring TCIP/IP and Telnet/Web settings is required.
Restart and reset to factory
defaults, except network
Same action as “Restart and reset to factory defaults” described directly above, but
network protocol settings are not changed.
Restart and download
firmware via FTP
New versions of firmware can be uploaded using FTP. To begin an FTP upload
session, you must first configure the FTP host address, username/password, filename,
and filepath.
When initiating an FTP upload session, the PRO2 restarts and uploads the firmware file
specified with the FTP filename command from the previously configured FTP host.
Restart and generate a new
X.509 certificate
Generates a new X.509 certificate issued and signed by a certificate-authority.
Restart and compute new SSH
keys
Generates new private and public SSH keys with the proper location and permisssion.