Server Technology switched pro2 User Manual - page 79
of
213
Switched PRO2 – User Guide
Using the Web Interface
•
79
Configuring Humidity Sensors Thresholds
Click the humidity sensor thresholds link at the bottom of the Sensors page to display the configuration page:
To set humidity sensor thresholds:
1. Provide the threshold hysteresis between event state and recovery(%RH). Range is 0-20%RH; default is
2%RH.
2. Set the low/high alarm and low/high warning threshold values for the humidity sensor(%RH). Range is min
0%RH, max100%RH.
3. Click Apply.