set line
Sets line configuration values.
Command Syntax
set line email [disabled | enabled]
set line load [alarmhi | alarmlo | warnhi | warnlo]
set line load hyst
set line snmpt [disabled | enabled]
Parameters
The set line command uses the following parameters:
Email notification for line events.
Hyst
Hysteresis between event state and recovery.
Load
Current load for a line. min = 0A, max (current limit) in show lines
command, hyst 0.0-10.0A (default 1.0A).
SNMPT
SNMP trap notifications for line events.
Sub-Parameters
The set line command uses the following sub-parameters:
alarmhi
High alarm value.
alarmlo
Low alarm value.
warnhi
High warning alarm.
warnlo
Low warning alarm.
min
Command Access
Admin level only
set loadshed