Server Technology switched pro2 User Manual - page 57
Switched PRO2 – User Guide
Using the Web Interface
•
57
Configuring Cord Power Thresholds
Click the power thresholds link at the bottom of the Cords page to display the configuration page:
To set power thresholds:
1. Provide the threshold hysteresis between event state and recovery (W). Range is 0-1000W; default is
100W.
2. Set the low/high alarm and low/high warning threshold values (W). Cord power does not include power
factor. Range is min 0W; max is power capacity shown in cstat command.
3. Click Apply.
Configuring Cord Apparent Power Thresholds
Click the apparent power thresholds link at the bottom of the Cords page to display the configuration page: