Server Technology switched pro2 User Manual - page 191
Switched PRO2 – User Guide
Using the Command Line Interface (CLI)
•
191
show outlets
Shows outlet configuration values.
Command Syntax
show outlets
Command Access
Admin level only
Example
Switched CDU: show outlets
SNMP Email Max
ID Outlet Name Notif. Notif. Current
-- ----------- ------ ------ -------
AA1 Master_Outlet_1 enabled enabled 20A
AA2 Master_Outlet_2 enabled enabled 15A
AA3 Master_Outlet_3 enabled enabled 15A
Extra On Wakeup Locked PF PF
ID Delay State No-Ctl Lo-Alrm Lo-Warn
-- -------- ------ ------ ------- -------
AA1 0 sec On No 0.70 0.80
AA2 0 sec On No 0.70 0.80
AA3 0 sec On No 0.70 0.80
Current Current Current Current Power Power Power Power
ID Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm
-- ------- ------- ------- ------- ------- ------- ------- -------
AA1 0.0A 0.0A 14.0A 16.0A 0W 0W 2912W 3328W
AA2 0.0A 0.0A 10.5A 12.0A 0W 0W 2184W 2496W
AA3 0.0A 0.0A 10.5A 12.0A 0W 0W 2184W 2496W
Common Outlet Settings
Sequence Delay: 2 second(s)
Reboot Delay: 15 second(s)
Outlet State Change Logging: disabled
Outlet Current Hysteresis: 1.0A
Outlet Power Hysteresis: 10W
Outlet Power Factor Hysteresis: 0.02