Server Technology switched pro2 User Manual - page 44
Switched PRO2 – User Guide
Using the Web Interface
•
44
Monitoring > Sensors
The Sensors page provides a quick view of the operating status and color-coded graphic showing current
operating value of environmental sensors for temperature and humidity.
What to look for:
The operating status of all sensors should be Normal, and operating temperature or relative humidity should be
within defined thresholds.
Temperature Status
The Temperature graph displays a blinking warning or critical error whenever temperature exceeds low or high
threshold. The PRO2 continues to display the status until the condition changes or the issue has been resolved.
Temperature graph colors:
• Violet = coldest; low alarm (threshold configured by user)
• Blue = cold; low warning (threshold configured by user)
• Green = acceptable temperature range
• Yellow – warm; high warning (threshold configured by user)
• Red = hot; high alarm (threshold configured by user)
The default range of low/high temperature threshold values is
-40 to 123(C°)
. Temperature threshold values are
user-defined at Configuration > System > Sensors.
Humidity Status
The Humidity graph displays a blinking warning or critical error whenever humidity exceeds low or high threshold.
The PRO2 continues to display the status until the condition changes or the issue has been resolved.
Humidity graph colors:
• Violet = wettest; high alarm (threshold configured by user)
• Blue = wet; high warning (threshold configured by user)
• Green = acceptable percentage of relative humidity
• Yellow = dry; low warning (threshold configured by user)
• Red = driest; low alarm (threshold configured by user)
The default range of low/high relative humidity threshold values is 0-100%RH. Humidity threshold values are user-
defined at Configuration > System > Sensors.