Server Technology switched pro2 User Manual - page 167
Switched PRO2 – User Guide
Using the Command Line Interface (CLI)
•
167
extondelay
Sets an extra on delay when turning on an outlet. 0-900 seconds.
host
Sets the hostname for an outlet for script or shutdown actions.
0-63 characters.
hyst
Sets the hysteresis between event state and recovery.
load
Sets the current load for an outlet. min 0.0A, max (max current) in
show outlets command, hyst 1.0-10.0A (default 1.0A)
lineevent
Sets if load shedding (due to outlet current load events) is allowed for
an outlet.
lock
Sets if control actions are disabled for an outlet after wakeup state is
applied.
pf
Sets the power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02)
rebootdelay
Sets an extra on delay when rebooting an outlet (5-600 seconds).
script
Sets to additionally send request to have shutdown agent run a script
before shutting down the host.
sensoraction
Sets the load shedding outlet control action for all sensor alarm events.
seqdelay
Sets the delay between turning on outlets. 0-15 seconds.
shutdown
Sets if notification of pending off state of outlet is sent to outlet host
before changing state.
shutdown delay
Sets the remote shutdown delay for an outlet. 1-900 seconds.
snmpt
Sets if SNMP trap notifications for outlet events.
tempevent
Sets if load shedding (due to temperature sensor events) is allowed for
an outlet.
upsevent
Sets if load shedding (due to UPS events) are allowed for an outlet.
wakeup
Sets the default outlet control state after system power up.
waterevent
Sets if load shedding (due to water sensor events) is allowed for an
outlet
watts
Sets the power (without power factor).min 0W, max (power capacity) in
ostat details, hyst 0-1000W (default 10W).