Server Technology switched pro2 User Manual - page 39
Switched PRO2 – User Guide
Using the Web Interface
•
39
Monitoring > Branches
The Branches page displays branch status that supports the standard Branch Current Monitoring feature of the
PRO2. Branch Current Monitoring allows the configuration of thresholds on the branch circuit to provide notification
before a breaker trips. Displayed on the page are branch current (A), percentage of current utilized, and threshold
status.
Note: The PRO2 allows the capability to load-shed based on branch current status.
What to look for:
Branch names are set internally on the PRO2 at factory assembly and cannot be changed. Branch operations
status should be Normal and branch current should be within defined thresholds. Branch threshold range values
are affected by changing the current capacity of an over-current protector (OCP).
The branch status and branch current status displays a blinking warning (yellow) and red (error condition) when a
branch exceeds the user-defined thresholds. The branch continues to display yellow and red states until the
condition changes or the issue has been resolved.
Branch current thresholds are user-defined at Configuration > System > Branches.