Server Technology switched pro2 User Manual - page 192
Switched PRO2 – User Guide
Using the Command Line Interface (CLI)
•
192
show phases
Shows phase configuration values.
Command Syntax
show phases
Command Access
Admin level only
Example
Switched CDU: show phases
ID Phase Name
-- ----------
AA1 AA:L1-L2
AA2 AA:L2-L3
AA3 AA:L3-L1
SNMP Email Nominal
ID Notif. Notif. Voltage
-- ------ ------ -------
AA1 enabled enabled 208V
AA2 enabled enabled 208V
AA3 enabled enabled 208V
Voltage Voltage Voltage Voltage PF PF
ID Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm Lo-Alrm Lo-Warn
-- ------- ------- ------- ------- ------- -------
AA1 187.2V 197.6V 218.4V 228.8V -- --
AA2 187.2V 197.6V 218.4V 228.8V -- --
AA3 187.2V 197.6V 218.4V 228.8V -- --
Common Phase Settings
Phase Voltage Hysteresis: 2.0V
Phase Power Factor Hysteresis: 0.02
show ports
Shows port configuration values.
Command Syntax
show ports
Command Access
Admin level only
Example
Switched CDU: show ports
ID Port Name Locked Baud Timeout DSR Chk
-- --------- ------ ---- ------- -------
COM1 Console No 9600 5 min enabled
COM2 Aux No 115200 5 min enabled