182
show cords
Shows cord configuration values.
Command Syntax
show cords
Command Access
Admin level only
Example
Switched CDU: show cords
ID Cord Name
-- ---------
AA Master_Cord_A
BA Link_Cord_A
SNMP Email User / Factory User / Factory
ID Notif. Notif. Current Capacity Nominal Voltage
-- ------ ------ ---------------- ---------------
AA enabled enabled 30A / 30A 230V / 230V
BA enabled enabled 30A / 30A 230V / 230V
Power Power Power Power Balance Balance
ID Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm Hi-Warn Hi-Alrm
-- ------- ------- ------- ------- ------- -------
AA 0W 0W 14490W 16560W 15% 20%
BA 0W 0W 14490W 16560W 15% 20%
App Pwr App Pwr App Pwr App Pwr PF PF
ID Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm Lo-Alrm Lo-Warn
-- ------- ------- ------- ------- ------- -------
AA 0VA 0VA 14490VA 16560VA 0.70 0.80
BA 0VA 0VA 14490VA 16560VA 0.70 0.80
Common Cord Settings
Cord Power Hysteresis: 100
Cord Apparent Power Hysteresis: 100
Cord Power Factor Hysteresis: 0.0
Cord 3-Phase Out-Of-Balance Hyst: 2%