show loadshed
Shows load shedding configuration values.
Command Syntax
show loadshed
Command Access
Admin level only
Example
Switched CDU: show loadshed
General load shedding options: Status Action Delay
UPS On-Battery Load Shedding: disabled 0 minute(s)
UPS On-Utility Auto Recovery: enabled 0 minute(s)
Line Load Shedding: disabled
Branch Load Shedding: disabled
Sensor Load Shedding: disabled
Line shedding event settings:
ID Line Name On-Bat Shed High Current
-- --------- ----------- ------------
AA1 AA:L1 disabled 24.0A
BA1 BA:L1 disabled 24.0A
Sensor shedding event settings:
ID Sensor Name Type Auto-Rec High Temp
-- ----------- ---- -------- ---------
E1 Contact_Sensor_E1 CS disabled --
E2 Contact_Sensor_E2 CS disabled --
E3 Contact_Sensor_E3 CS disabled --
E4 Contact_Sensor_E4 CS disabled --
A1 Temp_Sensor_A1 TS disabled 50C
A2 Temp_Sensor_A2 TS disabled 50C
B1 Temp_Sensor_B1 TS disabled 50C
B2 Temp_Sensor_B2 TS disabled 50C
E1 Temp_Sensor_E1 TS disabled 50C
E2 Temp_Sensor_E2 TS disabled 15C
E1 Water_Sensor_E1 WS disabled --
Outlet load shedding events:
-Enabled Load-Shed Events-
ID Outlet Name UPS Line Branch
AA1 Master_Outlet_1 - - -
AA2 Master_Outlet_2 - - -
AA3 Master_Outlet_3 - - -
AA4 Master_Outlet_4 - - -
AA5 Master_Outlet_5 - - -