Server Technology switched pro2 User Manual - page 80
Switched PRO2 – User Guide
Using the Web Interface
•
80
Configuring Temperature Sensors Thresholds
Click the temperature sensor thresholds link at the bottom of the Sensors page to display the configuration page:
To set temperature sensor thresholds:
1. Provide the threshold hysteresis between event state and recovery temperature. Range is 0-30
Celsius,
or 0-54
Fahrenheit; default is 1 Celsius or 2 Fahrenheit.
2. Set the low/high alarm and low/high warning threshold values for the temperature sensor(
). Range is
minimum -40
to maximum 123 Celsius, or minimum -40 to maximum 253 Fahrenheit.
3. Click Apply.