Server Technology switched pro2 User Manual - page 194
Switched PRO2 – User Guide
Using the Command Line Interface (CLI)
•
194
show sensors
Shows sensor configuration values.
Command Syntax
show sensors
Command Access
Admin level only
Example
Switched CDU: show sensors
Sensor ID Sensor Name
------ -- -----------
Temp A1 Temp_Sensor_A1
Temp A2 Temp_Sensor_A2
Temp C1 Temp_Sensor_C1
Temp C2 Temp_Sensor_C2
Humid A1 Humid_Sensor_A1
Humid A2 Humid_Sensor_A2
Humid C1 Humid_Sensor_C1
Humid C2 Humid_Sensor_C2
Contact C1 Contact_Sensor_C1
Contact C2 Contact_Sensor_C2
Contact C3 Contact_Sensor_C3
Contact C4 Contact_Sensor_C4
Water C1 Water_Sensor_C1
ADC C1 ADC_Sensor_C1
SNMP Email
Sensor ID Notif. Notif. Lo-Alrm Lo-Warn Hi-Warn Hi-Alrm
------ -- ------ ------ ------- ------- ------- -------
Temp A1 enabled enabled 1C 5C 45C 50C
Temp A2 enabled enabled 1C 5C 45C 50C
Temp C1 enabled enabled 1C 5C 45C 50C
Temp C2 enabled enabled 1C 5C 45C 50C
Humid A1 enabled enabled 5% RH 10% RH 90% RH 95% RH
Humid A2 enabled enabled 5% RH 10% RH 90% RH 95% RH
Humid C1 enabled enabled 5% RH 10% RH 90% RH 95% RH
Humid C2 enabled enabled 5% RH 10% RH 90% RH 95% RH
Contact C1 enabled enabled -- -- -- --
Contact C2 enabled enabled -- -- -- --
Contact C3 enabled enabled -- -- -- --
Contact C4 enabled enabled -- -- -- --
Water C1 enabled enabled -- -- -- --
ADC C1 disabled disabled 0 0 255 255
Common Sensor Settings
Temperature Scale: Celsius
Temperature Sensor Hysteresis: 1C
Humidity Sensor Hysteresis: 2% RH
ADC Sensor Hysteresis: 1