Setting Branch Current Thresholds
From the Branches page, click the link Branch Current Thresholds to display the related thresholds edit page:
To set branch current thresholds:
1. Set the threshold hysteresis value (in Amps). Hysteresis is the values between the event state and
recovery. Provide 0.0 to 10.0A. Default is 1.0A.
2. Provide the current load (A) for low/high warning/alarm threshold for a displayed branch on the page. Valid
range is between 0-max (Max Current) in show branches command.
3. Click Apply.