Server Technology switched pro2 User Manual - page 83
Switched PRO2 – User Guide
Using the Web Interface
•
83
Shutdown and Smart Load Shedding
The Smart Load Shedding feature allows the load shedding of outlet loads, both on CDU and PRO2 products,
based on UPS condition (on-battery), temperature level, and input current load.
The Shutdown feature for Switched products is also supported by the extended license-key feature Smart Load
Shedding. A systematic shutdown is initiated by Smart Load Shedding events such as high temperature, high
infeed load, and UPS “on battery” conditions.
Supported Operating Systems for Shutdown
Remote Shutdown Agents are available for the following operating systems:
• Windows: 2000, 2003, XP.
• Linux: Red Hat 7.3, 8.0; Red Hat Enterprise 2.1 ES (update 5); 3.0 ES (update 4); Novell SUSE Linux
Enterprise Server.
• Unix: HP-UX 11.0, 11i v1, 11i v2; IBM AIX 4.3, 5.3; Sun Solaris 8, 9, 10.
• Novell Netware: 6
Installing the Shutdown Agent
Note: For all operating systems shown below, if the IP address of the PRO2 is left blank in the last step of
these installation instructions, any PRO2 can send a shutdown signal to the server.
Windows
1. Browse to the location of the Remote Shutdown Agent installation files.
2. Run setup.exe by double-clicking the icon.
3. Reply to the standard installation prompts.
4. For additional security, when prompted, enter the IP address of the PRO2 that will be sending the
shutdown signal.
Linux
1. Browse to the location of the Remote Shutdown Agent installation files.
2. Run SetupRA.
3. For additional security, when prompted enter the IP address of the PRO2 that will be sending the
shutdown signal.
Unix
1. Browse to the location of the Remote Shutdown Agent installation files.
2. Run Install.
3. For additional security, when prompted enter the IP address of the PRO2 that will be sending the
shutdown signal.
Novell Netware
1. Browse to the location of the Remote Shutdown Agent installation files.
2. From the NetWare system console, load the configuration module (pmconfig.nlm) using the default
path.
3. For additional security, when prompted enter the IP address of the PRO2 that will be sending the